Skip to Main Content
Site IDParent SiteLocationCountyEFO
5621White House STP725 Industrial DriveRobertsonNashville

Inspection Details

49487
5621
TN0059404
9/24/2015
Sanitary Sewer Overflow Non-Sampling
Out of Compliance
Pump stations fenced/locked & in generally in good condition with few maintenance problems, 10 total pump stations (2 vacuum, 8 regular pumps), stations all have telemetry & are checked once per week, past records of station inspections were inadequate, currently not keeping any documentation/records of pump station inspections, I/I causing some problems but few overflow events occurring, overflows are reported to DWR, rehabilitation of sewers on-going, need to maintain better records of flows/overflows before & after each rehabilitation project, all stations have potable water supply & backflow preventers had been removed at 2 stations.