Skip to Main Content
Site IDParent SiteLocationCountyEFO
6412Harpeth Valley Utility District STP4063 Old Hickory Blvd.DavidsonNashville

Inspection Details

57730
6412
TN0074748
5/1/2018
Compliance Biomonitoring (CBI)
In Compliance
Facility is well maintained and operated. No concerns were noted during the site review. Some minor issues noted in laboratory records: had not been running duplicate samples for E.coli analysis; not collecting biomonitoring grab samples at 6 hour intervals. Records are well organized and appear to be reporting pertinent information. Awaiting sampling results from ESC. 5/2/18
Received analysis results from ESC-reported >7.2% for Pimephales promelas. Due to inconsistencies in the lab data for Ceriodaphnia dubia, the result was reported as invalid. This is not considered a failure of the biomonitoring test and no issues were noted during the inspection that would indicate toxicity of the effluent. 5/17/18