Skip to Main Content
Site IDParent SiteLocationCountyEFO
6412Harpeth Valley Utility District STP4063 Old Hickory Blvd.DavidsonNashville

Inspection Details

49292
6412
TN0074748
1/29/2016
Compliance Eval (non-sampling) (CEI)
In Compliance
Facility & site in good condition, well maintained. All treatment units in operation & functioning properly. De-nitrification zone, then oxidation ditches with aerators adjusted to get optimum treatment. Effluent of good quality & meeting permit limits. Only 1 BOD & 1 TSS violation in past 2 years. Some overflow events, but there is on-going collection system rehabilitation program to address I/I. Records & reports are acceptable. Flow meter & other self-monitoring & lab equipment calibrated annually as required. Some problems with BOD initial DO being supersaturated & problems with polyseed blank depletion. Use of polyseed is not necessary & will be stopped, samples are collected before UV disinfection & don't require seeding. Staff gauge in Parshall flume & effluent flow meter sensor are not aligned properly, needs adjustment.