Skip to Main Content
Site IDParent SiteLocationCountyEFO
5835Erin STP / WWTP187 Industrial Park RdHoustonNashville

Inspection Details

25191
5835
TN0064882
8/31/2011
Compliance Sampling (CSI)
NOV
8/3/11 & 9/1/11, split samples with operator, major items out of service (all blowers out of service 1st day, one blower working/new motor 2nd day, influent flow meter out of service, refrigerator on influent sampler out of service), also effluent sampler refrigerator not working properly, now using solution chlorine feed for disinfection, chlorine room repairs not made yet (power, heat & vent fan not working, hole eaten in floor by chlorine leaks not repaired, corroded door/wall panel not replaced, ceiling not repaired), filter funnel for e-coli & suspended solids analysis needs replacement, not calibrating chlorine residual colorimeter with standards, not following all steps of some analysis procedures, no records of sludge wasting to drying beds and hauled to landfill, poor operation and maintenance (treatment units severely corroded, rusted through safety rails not replaced, corroded walkway grills not replaced, corroded influent weir structure not replaced, have replaced influent splitter weirs, now using both aeration basins.