Inspection Details
Site ID
Parent Site
Location
County
EFO
6397
Pegram STP
5227 Walkup Road
Cheatham
Nashville
Inspection Details
Inspection Number
117961
Site ID
6397
Permit Number
TN0074586
Inspection date
7/2/2024
Inspection type
Compliance Eval (non-sampling) (CEI)
Status
Out of Compliance
Notes
Standing sewage on sand filter with untreated waste discharging from side of filter. Strong wastewater odor. Dripfield failing across multiple zones with ponding water and algae growth. Potential for overland flow to enter waters of the state at the Harpeth river. Use of heavy agricultural equipment on active drip including fertilizer trucks stuck in drip field causes deep divots in soil with standing water and system damage. Pegram/Kingston springs has received 0.08" of rain in the previous 5 days with 0" in the 24-hours prior to the survey. Photo included to show vegetation height and density preventing thorough inspection by operator and inspectors.