Skip to Main Content
Site IDParent SiteLocationCountyEFO
5621White House STP725 Industrial DriveRobertsonNashville

Inspection Details

43745
5621
TN0059404
9/22/2015
Compliance Eval (non-sampling) (CEI)
Out of Compliance
Treatment units all in operation, oxidation ditch has small trees/vegetation growing on accumulated solids masses around valves, sludge pump for one clarifier out of service/repairs planned next day, influent wastewater is very septic due to excessive time in collection system (up to 30 days), wastewater is very dark color throughout the plant, effluent appeared to be meeting permit limits, some sewage type solids observed just downstream of the outfall point, influent & effluent composite samples are not proportional-to-flow, plant upgrade will have corrective measures added for sampling, some E. coli analysis data at greater than required frequency was not reported/or not reported properly for 2 months, E. coli incubator and drying oven need better temperature control, records on file for 3+ years and are adequate to meet permit conditions, review of MORs/DMRs found violations of permit limits for ammonia, DO, TSS, T. nitrogen, T. phosphorus, CBOD, and bio-monitoring.