Skip to Main Content
Site IDParent SiteLocationCountyEFO
4912Smyrna STP100 Jack Hunter DriveRutherfordNashville

Inspection Details

89446
4912
TN0020541
3/24/2021
Compliance Eval (non-sampling) (CEI)
Out of Compliance
Facility disinfects with UV but occasionally adds chlorine; does not sample or report chlorine residual as required by permit. Facility bypassed all headworks to accommodate construction, did not report bypass. Has had numerous effluent violations, largely related to poor settling sludge and discharge of clarifier solids. Dealing with filamentous bacteria and settling issues exacerbated by poor operational methods. Operators demonstrated poor understanding of permit requirements and operational controls.