Skip to Main Content
Site IDParent SiteLocationCountyEFO
5080Grand Junction Oxidation Pond720 Park Swain RoadHardemanMemphis

Inspection Details

75788
5080
TN0022560
12/8/2021
Compliance Eval (non-sampling) (CEI)
Out of Compliance
35 exceedances of E. Coli during evaluation period from January 1, 2019 through November 30, 2021. Effluent not being disinfected. Disinfection system has been taken out of use for years. No DO meter at the facility. Lots of I&I during rain events.