Skip to Main Content
Site IDParent SiteLocationCountyEFO
73511METRO WATER SERVICES1600 2nd Av NDavidsonNashville

Inspection Details

72350
73511
4/24/2018
Sanitary Survey
Out of Compliance
At the Omohundro plant several times a turbidimeter verification indicated calibration should have been required but was not done. Calibration records were not signed by the responsible person