DWR Inspections
Inspection Details
Site ID
Parent Site
Location
County
EFO
99536
Mason Water Dept
12161 Main St
Tipton
Memphis
Inspection Details
Inspection Number
56471
Site ID
99536
Permit Number
Inspection date
2/13/2018
Inspection type
Sanitary Survey
Status
Out of Compliance
Notes
Well 3 running on temporary pump. Wells 1 and 2 not operating. No back up well. Wellhead Protection Plan not submitted since 2012. Cross Contamination program not being enforced. Clear well not professionally inspected. Master flow meter pit full of water, sump broken. No SOP for system operations. No flushing since spring 2016. Still no on-site certified operator.