Skip to Main Content
Site IDParent SiteLocationCountyEFO
99536Mason Water Dept12161 Main StTiptonMemphis

Inspection Details

56471
99536
2/13/2018
Sanitary Survey
Out of Compliance
Well 3 running on temporary pump. Wells 1 and 2 not operating. No back up well. Wellhead Protection Plan not submitted since 2012. Cross Contamination program not being enforced. Clear well not professionally inspected. Master flow meter pit full of water, sump broken. No SOP for system operations. No flushing since spring 2016. Still no on-site certified operator.