DWR Inspections
Inspection Details
Site ID
Parent Site
Location
County
EFO
4912
Smyrna STP
100 Jack Hunter Drive
Rutherford
Nashville
Inspection Details
Inspection Number
107917
Site ID
4912
Permit Number
TN0020541
Inspection date
2/3/2023
Inspection type
Compliance Sampling (CSI)
Status
In Compliance
Notes
Still waiting on sampling results from lab. Plant has almost completed major upgrade increasing size as well as adding anaerobic and anoxic zones, and tertiary filtration for nutrient removal. Solids processing has replaced belt presses with centrifuges. Plant appeared to be in good condition, sludge blankets ~ 2 ft in clarifiers, ox ditches had minimal foam. Some pin floc in clarifiers, effluent appeared clear and was odorless. No apparent impact to receiving stream. Facility experienced treatment interference culminating in complete plant upset and loss of treatment from approx Jan-June 2022 due to industrial discharges. Responsible industry has been addressed under Smyrna's pretreatment program. Effluent exceedances relating to this event were addressed under a previous NOV from the Division and responded to by Smyrna.