DWR Inspections
Inspection Details
Site ID
Parent Site
Location
County
EFO
4916
Greenbrier STP
1223 Sugar Camp Dr
Robertson
Nashville
Inspection Details
Inspection Number
39696
Site ID
4916
Permit Number
TN0020621
Inspection date
5/5/2014
Inspection type
Compliance Biomonitoring (CBI)
Status
Notice of Deficiency
Notes
Site visit 5/1/14 to confirm composite sampler operation & plant walk thru.
Eff was clear & no problems noted w/plant operation.
Noted that flow from plant PS by drying beds pumped U/S of inf flow meter & sampling.
Samples were collected May 5-9, 2014 using the STP eff composite sampler.
Passed both Cd & Pp testing.
Determined there was a problem with STP biomonitoring sampling for their tests.
Samples collected by time composite & therefore aliquots collected from standing water between SBR decant cycles.