10/6/2022
Sanitary Survey
In Compliance
Deficiencies noted. Storage tank remediation is needed, the system is acquiring bids for tank rehab or replacement. I observed a gap between the clearwell hatch lid and surface of the clearwell. A gasket is needed to prevent contamination. Water from cleaning activities at filter room is dripping through core drill holes to the pipe gallery below causing corrosion and rust. No SCBA provided for operators to change chlorine cylinders.