Skip to Main Content
Site IDParent SiteLocationCountyEFO
5217Cartwright Creek - Grasslands STPRiver Rest SubdivisionWilliamsonNashville

Inspection Details

42045
5217
TN0027278
2/11/2014
Compliance Eval (non-sampling) (CEI)
NOV
Review of 2013 MORs & DMRs showed some reporting problems - wrong numbers entered & improper calculations.
Total N & P not run from Feb 2013 thru Oct 2013.
Insoluble TKN & P not run May 2013 thru Oct 2013.
Problems with inf & eff flow meters in Jan 2014 - temp eff meter in place.
Inf & eff samplers paced by time due to flow meter problems.
Some STP operational problems due to very cold weather.
2 of 3 pump stations were being checked monthly - should be daily.
Checked on SSO reported 2/5/14.
Some CS problems & SSOs due to I/I.