In Compliance
Site visit conducted to assist Mike Petty in getting laboratory set-up. Present were Mike Petty and Mike Caudill from Claiborne UD. Ken Mazingo was also present. Initially, free chlorine residual was low leaving the WTP at around 0.4 mg/L. Claiborne staff adjusted chlorine residual flow and flushed clarifiers and was able to adjust effluent chlorine to above 3.0 mg/L before leaving. Discussed Drinking Water Monitoring Program and was able to restore flow to combined filter effluent turbidimeter and calibrate continuous chlorine analyzer. Mike Petty had developed a daily worksheet to document plant readings.