Inspection Details
Site ID
Parent Site
Location
County
EFO
5781
Celina STP
100 Wastewater Road
Clay
Cookeville
Inspection Details
Inspection Number
59553
Site ID
5781
Permit Number
TN0063886
Inspection date
12/1/2017
Inspection type
Compliance Eval (non-sampling) (CEI)
Status
Out of Compliance
Notes
The effluent flow meter has been out of operation for 3 months.
Recently BOD violations have been occurring.
The D.O. meter was reviewed and found to be in the need of maintenance.
City needs to provide industrial waste surveys to selected area businesses.
Discussed core (sludge judge) sampling and cleaning of ponds.