Skip to Main Content
Site IDParent SiteLocationCountyEFO
5188Watertown STP106 S Commerce RdWilsonNashville

Inspection Details

19977
5188
TN0025488
12/1/2009
Pretreatment Compliance (oversight)
Minor Deficiency Noted
IU permit
- add provision for TTO cert statement.
- need justification for grab sample requirement.
- better explain 'in-house monitorin'.
- repeat sample req is 30 days after becoming aware of violation not 30 days after the violation.
IU sampling using cut off 2 liter bottle on pole not valid.
need to document review of IU sample results.